Bulletin 609 Single and Three Phase
|
Bulletin 609
- Contact position indicator
- Locking features
- Wide range of enclosures:
Open-type without enclosure, Type 1, and Type 12
Bulletin 609 manual starting switches are designed for use on motor starting installations where remote push button control is not required and where undervoltage protection is not needed. The motor is started at full line voltage, and thermal type overload protection is provided.
Bulletin 609RS manual starting switches are designed for manually reversing AC polyphase motors; the Bulletin 609TS manual switches are designed for operating 2-speed, separate winding wye connected motors. These switches incorporate two of the standard Bulletin 609 manual starting switches mounted on a common base plate. A mechanical interlock is provided to prevent both switches from being closed at the same time.
| Table of Contents |
| Product Selection |
| Accessories and Modifications |
| Approximate Dimensions |
Standards Compliance and Certifications
Standards Compliance
- NEMA/EEMAC ICS2
(Industrial Controls and Systems)
- UL 508
- EN60947-4-1
- ABS 4/5.115
- USCG 46
- CFR 111.70
Certifications
- UL Listed (File No. E14841;
Guide No. NLRV)
- CSA Certified (File LR 1234)
- American Bureau of Shipping (ABS)
- CE Marked
- Hazardous Location:
UL Listed (File No. E10314)
CSA Certified (File LR 11924)
Your order must include: 1) Cat. no. of the switch, 2) Cat. no. of the heater element(s), and 3) if required, cat. no. of any accessories.
Product Selection
Single- and Three-Phase NEMA Manual Starting Switches
| Type of Oper- ator |
Phase | Size | Maximum Horsepower Rating | Open Type without Enclosure |
Type 1 General Purpose Enclosure Surface Mounting¬ |
Type 12 Dusttight Industrial Use Enclosure |
Type 4/4X Watertight, Corrosion- Resistant Enclosure Fiberglass- Reinforced Polyester |
Hazardous Locations | |||||||
| Motor Voltage | Enclosure Class I, Groups C & D Class II, Groups E, F & G Divisions 1 & 2 |
||||||||||||||
| AC, 60 Hz |
AC, 50 Hz |
DC | Type 7 & 9 | Type 3R, 7 & 9§ | |||||||||||
| 115V | 200V | 230V | 460… 575V |
380… 415V |
115… 125V |
230… 250V |
Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | |||
| Push Button | 1 Æ | 0 | 1 | — | 2 | — | — | — | — | 609-AOX | 609-AAX | 609-AJX | 609-ACX | 609-AEX | 609-AHX |
| 1 | 2 | — | 3 | — | — | — | — | 609-BOX | 609-BAX | 609-BJX | 609-BCX | 609-BEX | 609-BHX | ||
| 1 P | 3 | — | 5 | — | — | — | — | 609-XOX | 609-XAX | 609-XJX | 609-XCX | 609-XEX | 609-XHX | ||
| 3 Æ | 0 | — | 3 | 3 | 5 | 5 | — | — | 609-AOW | 609-AAW | 609-AJW | 609-ACW | 609-AEW | 609-AHW | |
| 1 | — | 7-1/2 | 7-1/2 | 10 | 10 | — | — | 609-BOW | 609-BAW | 609-BJW | 609-BCW | 609-BEW | 609-BHW | ||
| Toggle Lever | 1 Æ | 0 | 1 | — | 2 | — | — | — | — | 609T-AOX | 609T-AAX | — | — | — | — |
| 1 | 2 | — | 3 | — | — | — | — | 609T-BOX | 609T-BAX | — | — | — | — | ||
| 1 P | 3 | — | 5 | — | — | — | — | 609T-XOX | 609T-XAX | — | — | — | — | ||
| 3 Æ | 0 | — | 3 | 3 | 5 | 5 | — | — | 609T-AOW | 609T-AAW | — | — | — | — | |
| 1 | — | 7-1/2 | 7-1/2 | 10 | 10 | — | — | 609T-BOW | 609T-BAW | — | — | — | — | ||
| Push Button | DCT | 0 | — | — | — | — | — | 1 | 1-1/2 | 609D-AOZ | 609D-AAZ | — | 609D-ACZ | 609D-AEZ | 609D-AHZ |
| 1 | — | — | — | — | — | 1-1/2 | 2 | 609D-BOZ | 609D-BAZ | — | 609D-BCZ | 609D-BEZ | 609D-BHZ | ||
| Toggle Lever | DCT | 0 | — | — | — | — | — | 1 | 1-1/2 | 609DT-AOZ | 609DT-AAZ | — | — | — | — |
| 1 | — | — | — | — | — | 1-1/2 | 2 | 609DT-BOZ | 609DT-BAZ | — | — | — | — | ||
| Bulletin 609RS — Manual Reversing Switches | |||||||||||||||
| Push Button | 3 Æ | 0 | — | 3 | 3 | 5 | 5 | — | — | 609-AOW21 | 609-AAW21 | — | — | — | — |
| 1 | — | 7-1/2 | 7-1/2 | 10 | 10 | — | — | 609-BOW21 | 609-BAW21 | — | — | — | — | ||
| Toggle Lever | 3 Æ | 0 | — | 3 | 3 | 5 | 5 | — | — | 609T-AOW21 | 609T-AAW21 | — | — | — | — |
| 1 | — | 7-1/2 | 7-1/2 | 10 | 10 | — | — | 609T-BOW21 | 609T-BAW21 | — | — | — | — | ||
| Bulletin 609TS — Manual 2-Speed Switches | |||||||||||||||
| Push Button | 3 Æ | 0 | — | 3 | 3 | 5 | 5 | — | — | 609-AOW22 | 609-AAW22 | — | — | — | — |
| 1 | — | 7-1/2 | 7-1/2 | 10 | 10 | — | — | 609-BOW22 | 609-BAW22 | — | — | — | — | ||
| Toggle Lever | 3 Æ | 0 | — | 3 | 3 | 5 | 5 | — | — | 609T-AOW22 | 609T-AAW22 | — | — | — | — |
| 1 | — | 7-1/2 | 7-1/2 | 10 | 10 | — | — | 609T-BOW22 | 609T-BAW22 | — | — | — | — | ||
| ¬ Type 1 general purpose flush mounting enclosures with pull box are also available. Order as follows. Change the second letter of the listed cat. no. from A to L. Example: Cat. No. 609-ALX. For a stainless steel flush plate, change the second letter of the listed cat. no. from A to Q. Example: Cat. No. 609-AQX. | |||||||||||||||
| T DC manual starters are not UL listed. | |||||||||||||||
| Fiberglass-reinforced polyester hubs are included with each starter. | |||||||||||||||
| § These enclosures include a cover gasket and drain. It is recommended that a breather also be installed. | |||||||||||||||
| Breather | Cat. No. 1401-N1 | (Can be installed at the top of an enclosure.) |
| Drain | Cat. No. 1401-N2 | (Can be installed at the bottom of an enclosure.) |
| Breather-Drain Combination | Cat. No. 1401-N3 | (Can be installed at the top of an enclosure as a breather or bottom as a drain.) |
Accessories
Pilot Light Kits
Kits are available for field installation of pilot lights in Type 1 General Purpose surface or flush mounting enclosures. As standard, a clear pilot light lens is supplied. Pilot lights are not available for Bulletin 609RS or 609TS manual starters.
| Volts [V] | Cat. No. |
| 120 | 609-N10 |
| 240 | 609-N20 |
| 480 | 609-N40 |
| 600 | 609-N60 |
Pilot Lights Factory Installed
To order, add the following suffix code after the last letter in the listed Cat. No. Example: Cat. No. 609-AAXD4. Available for Type 1 General Purpose Enclosure only.
| Volts [V] | Suffix Code |
| 120 | D4 |
| 240 | A4 |
| 480 | B4 |
| 600 | C4 |
| Note:Replacement lamp is ANSI part number B2A (NE-51H), Cat. No. 609-N9. | |
Fusing
The Bulletin 609 is suitable for general installation in accordance with the local electrical code.
Group Fusing
The Bulletin 609 sizes 0 and 1 in Type 1, 4X, and 12 enclosures are UL Listed for group fusing with Class J fuses only. See table below for maximum fuse ratings.
| Full Load Current of Smallest Motor Amperes [A] |
Maximum Fuse Ratings [A] | |
| Nominal System Voltages | ||
| 120…240V | 480…600V | |
| 0.45…2.99 | 30 | 30 |
| 3.00…6.49 | 60 | 30 |
| 6.50…18.0 | 100 | — |
Approximate Dimensions
Bulletin 609 609U
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
NEMA Type 1
|
|
|
|
|||
| Surface Mounting | Flush Mounting for Plaster Wall | Flush Mounting for Machine Cavity | Flush Mounting Cavity and Drilling Layout |
NEMA Type 4/4X
|
|
|
| Open Type — Without Enclosure |
¬ Undervoltage solenoid applies only to Bulletins 609U and 609TU.
Bulletin 609 609U, Continued
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
NEMA Type 3R, 7 & 9
|
NEMA Type 7 & 9
|
NEMA Type 12
|
Bulletin 609RS, 609TS
Open Type Without Enclosure
|
NEMA Type 1
|